County approved permit plans are required on site for all inspections including reinspections.
This PROJECTION inspection is required prior to backfilling.
-
Foundation wall needs to sit entirely on footing, with no overhang.
-
An ideal projection is centered on the footing below.
-
A minimum 2″ projection is required on both sides. A 6″ min. is required on all four sides at fireplaces.
-
Both sides of the foundation are required to be open and free of mortar, dirt, debris, etc.
-
The amount of projection cannot exceed the thickness of the footing.
-
Bulkhead material used for footing step-downs shall be removed.